The equivalent circuit of any device can be quite helpful in predetermination of the behaviour of the device under various conditions of operation and it can be drawn if the equations describing its behaviour, are known. If any electrical device is to be analysed and investigated further for suitable modifications, its appropriate equivalent circuit is necessary.

The equivalent circuit for electromagnetic devices consists of a combination of resistances, inductances, capacitances, voltage etc. Such an equivalent circuit (or circuit model) can, therefore, be analysed and studied easily by the direct application of electric circuit theory.

As stated above, equivalent circuit is simply a circuit representation of the equations describing the performance of the device. The behaviour of the transformer under load and are helpful in arriving at the transformer equivalent circuit.

Equivalent circuit of a transformer having transformation ratio K = E2/E1 is shown in Fig. 10.17.

The induced emf in primary winding E1 is primary applied voltage V1 less primary voltage drop. This voltage causes iron loss current I0 and magnetising current Im and we can, therefore, represent these two components of no-load current by the current drawn by a non-inductive resistance R0 and pure reactance X0 having the voltage E1 or (V1—primary voltage drop) applied across them, as shown in Fig. 10.17.

Secondary current, I1 = I’1/K = I1 – I0 / K

Terminal voltage V2 across load is induced emf E2 in secondary winding less voltage drop in secondary winding.

The equivalent circuit can be simplified by transferring the voltage, current and impedance to the primary side. After transferring the secondary voltage, current and impedance to primary side equivalent circuit is reduced to that shown in Fig. 10.18.

The equivalent circuit diagram can further be simplified by transferring the resistance R0 and reactance X0 towards left end, as shown in Fig. 10.19. The error introduced by doing so is very small and can be neglected.

No-load current I0 is hardly 3 to 5 percent of the full-load rated current, the parallel branch consisting of resistance R0 and reactance X0 can be omitted without introducing any appreciable error in the behaviour of the transformer under loaded condition. Such a circuit is shown in Fig. 10.16 (a). The equivalent circuit referred to secondary side (neglecting no-load current I0) is illustrated in Fig. 10.15 (a).

Equivalent Resistance and Reactance:

ADVERTISEMENTS:

The two independent circuits of a transformer can be resolved into an equivalent circuit to make the calculations simple.

Let resistances and reactance of primary and secondary windings be R1 and R2 and X1 and X2 ohms respectively and let transformation ratio be K.

Resistive -drop in secondary winding = I2 R2

Reactive drop in secondary winding = I2 X2

ADVERTISEMENTS:

Resistive drop in primary winding = I1 R1

Reactive drop in primary winding = I1 X1

Referred To Secondary Side:

Since transformation ratio is K, so primary resistive and reactive drops as referred to secondary will be K times, i.e., K I1 R1 and K I1 X1 respectively. If I1 is substituted equal to KI2, then we have primary resistive and reactive drops referred to secondary equal to K2 I2 R1 and K2 I2 X1 respectively.

ADVERTISEMENTS:

Total resistive drop in a transformer = K2 I2 R1 + I2 R2 = I2 (K2 R1 + R2) = I2 R02

Total reactive drop in a transformer = K2 I2 X1 + I2 X2 = I2 (K2 X1 + X2) = I2 X02

The term (K2 R1 + R2) and (K2 X1 + X2) represent the equivalent resistance and reactance respectively of the transformer referred to secondary and let these be represented by R02 and X02 respectively. Equivalent circuit referred to secondary has been shown in Fig. 10.15 (a).

From phasor diagram [Fig. 10.15 (b)]

Where V2 is secondary terminal voltage, I2 is secondary current lagging behind the terminal voltage V2 by ɸ.

Since term (I2 X02 cos ɸ – I2, R0, sin ɸ) is very small as compared to the term (V2 + I2 R02 cos ɸ + I2 X02 sin ɸ), so neglecting the former we have-

K V1 = V2 + I2 R02 cos ɸ + I2 X02 sin ɸ

Or V2 = KV1 – I2 R02 cos ɸ – I2 X02 sin ɸ … (10.23)

Where V1 is applied voltage to primary winding.

If load is pure resistive, ɸ = 0 and V2 = KV1 – I2 R02 … (10.24)

If load is capacitive then ɸ should be taken as -ve hence we have:

V2 = KV1 – I2 R02 cos ɸ + I2 X02 sin ɸ … (10.25)

Referred To Primary Side:

Secondary resistive drop referred to primary:

Equivalent circuit referred to primary is shown in Fig. 10.16 (a)

From phasor diagram shown in Fig. 10.16 (b) we have:

clip_image045_thumb